100 Amp Wire Size & Voltage Drop Calculator (240V)

Live NEC Table 310.16 ampacity and Chapter 9 voltage drop calculator pre-loaded for a 100A 240V circuit (detached shops, ADUs, barn subpanels, and large home additions).

ADVERTISEMENT // CLS-LOCKED AD SLOT (BCS-WIRE-TOP-01)
728x90 DESKTOP / 320x100 MOBILE // PUBLISHER ca-pub-2977232003593293

Circuit Specification

NEC CH.9 + 310.16

Conductor Cross-Section & Drop Graph (SVG)

AWG + IEC MM2
LEFT: SCALED CORE DIAMETER VS 12 AWG REFRIGHT: VOLTAGE DROP SLOPE VS NEC LIMIT
Recommended Size
-
-
Actual Voltage Drop
-
-
Rated Ampacity
-
-
Conductor Heat Loss
-
-

NEC Sizing Notes for 100 Amp (240V) Circuits

Key NEC Rule: NEC Table 310.16 requires 3 AWG copper (100A) or 1 AWG aluminum (100A) for non-dwelling feeders, or 4 AWG Cu / 2 AWG Al under NEC 310.12 for whole-dwelling services.

Typical applications: detached shops, ADUs, barn subpanels, and large home additions. Overcurrent protection: 100A double-pole feeder breaker. Adjust the one-way distance slider above to verify whether voltage drop (>3%) forces upsizing your conductor one gauge thicker.

Embed This SVG Calculator: Contractors and home-improvement blogs can embed this interactive tool for free with one iframe snippet.

Live NEC AWG & IEC mm2 Comparison Matrix

AWG / kcmilMetric Area (IEC)NEC AmpacityVoltage DropLoad-End VoltageStatus
ADVERTISEMENT // CLS-LOCKED AD SLOT (BCS-WIRE-MID-02)
336x280 / 300x250 IN-CONTENT // PUBLISHER ca-pub-2977232003593293

NEC Ampacity Guides by Circuit Rating